Campus profile Operating

Central Ohio cluster

AWS · Google · Meta · Microsoft · New Albany / Hilliard / Dublin, Ohio

The resource footprint

Modelled average

In one day, this campus consumes about

11.750-metre swimming pools

Filled with the volume of water consumed by the campus and its electricity supply.

The actual estimate7,731,674 US gallons consumed

50-metre pools · 2 metres deep
Each diagram = 1 pool. Partial shading shows the remainder.
At the campus2,082,618 galMaking its electricity5,649,055 gal

Power-plant water may come from a different watershed. This is a volume comparison, not a claim that households lose this water.

At current operating capacity · Annual model spread evenly over time, not a live meter. Site estimates may differ by roughly ±40%.

Comparison sizes & sources

One pool = 50 × 25 × 2 metres = 2.5 million litres (about 660,430 US gallons). Pool depths vary; this is a defined comparison size.

One home-year = 10,791 kWh, the EIA’s 2022 average US residential electricity purchases. This excludes electricity generated at home and is a fixed US benchmark for all sites.

One car-year = 4.6 tonnes CO₂, the EPA’s typical passenger vehicle tailpipe estimate. The campus model is in CO₂e; the comparison expresses approximate climate scale, not equal mixtures of pollutants.

Monthly values are annual totals ÷ 12; daily values are annual totals ÷ 365. Actual demand varies. Comparisons cover the whole campus, including non-AI uses.

Water: see the numbers and sources

This is water used up, mainly through evaporation. Power-generation water may be used in a different watershed.

Total water use2,822M gal/yr
Evaporated on site760M gal
Making the power2,062M gal
Household comparison35,276homes, at 80,000 gal/year
Pressure on local water
Low-Medium — a regional measure of demand compared with available water
Where the water comes from
Municipal potable supply
Cooling
Mixed evaporative and closed-loop
Basis
Fitted to a published figure of 760 million gallons a year
Claimed vs observed
Google's 2025 Ohio campuses alone consumed 1,331 million gallons (New Albany 835.7, Lockbourne 359.5, Lancaster 135.8). That is already more than this cluster row's fitted 760 million, so the cluster figure is a lower bound.
Air: see the numbers and sources

The totals include nitrogen oxides, sulphur dioxide and fine particles. They cover both this site and the power plants supplying it.

Nitrogen oxides989t/yr
Sulphur dioxide1,717t/yr
Fine particulates156t PM2.5
Health (EPA)$166M/yr
Health range
$58.4–166 million a year. Lower bound is EASIUR national mid-range; upper is EPA benefit-per-ton at a ~$12M VSL.
Statistical deaths
13.8 a year at that VSL — a national-average conversion from tons, not a local concentration study.
Equals
1,235,817 cars of NOx
Where it burns
PJM RFC — Ohio / Penn.
Generation mix
Gas 48 · Nuclear 27 · Coal 20
Diesel backup
Diesel backup is not yet counted for this campus, so on-site air figures are a floor.
CO₂e
2,029 kt/yr — climate, not air quality
The project, approvals and community concerns
Who asked for it
All four major hyperscalers, each with its own campus
Who approved it
New Albany's pre-zoned business park; AEP Ohio's contested data center tariff, approved by PUCO in 2025, requires large loads to pay for 85% of subscribed capacity whether or not they use it
What it serves
AWS us-east-2, Google and Microsoft cloud regions, Meta app serving
IT capacity
900 MW current capacity / 2,500 MW full-build scenario

The AEP Ohio case is the most-cited regulatory precedent in the US: it established that data centers must post minimum-demand commitments so that other ratepayers aren't left holding the bill for capacity that never materialises.

ratepayer-cost dispute

Keep this guide handy

40.0500°, -82.9500°

Quote or share these estimates

Gigawatt Ledger (2026). Central Ohio cluster: water and air. https://gigawatt-ledger.pages.dev/site/columbusoh/. Modelled from disclosed capacity; site-level error ±40%.

Include the estimate’s date, whether it describes current or proposed capacity, and its uncertainty. Get an embeddable card.

Gigawatt Ledger · September 2026. Water and air figures are estimated from public records and disclosed capacity. How we calculate them · Use this in your community.