Campus profile Operating

Cumulus / Susquehanna

Amazon Web Services · Salem Township, Pennsylvania

The resource footprint

Modelled average

In one day, this campus consumes about

7.7450-metre swimming pools

Filled with the volume of water consumed by the campus and its electricity supply.

The actual estimate5,109,200 US gallons consumed

50-metre pools · 2 metres deep
Each diagram = 1 pool. Partial shading shows the remainder.
At the campus461,092 galMaking its electricity4,648,107 gal

Power-plant water may come from a different watershed. This is a volume comparison, not a claim that households lose this water.

At current operating capacity · Annual model spread evenly over time, not a live meter. Site estimates may differ by roughly ±40%.

Comparison sizes & sources

One pool = 50 × 25 × 2 metres = 2.5 million litres (about 660,430 US gallons). Pool depths vary; this is a defined comparison size.

One home-year = 10,791 kWh, the EIA’s 2022 average US residential electricity purchases. This excludes electricity generated at home and is a fixed US benchmark for all sites.

One car-year = 4.6 tonnes CO₂, the EPA’s typical passenger vehicle tailpipe estimate. The campus model is in CO₂e; the comparison expresses approximate climate scale, not equal mixtures of pollutants.

Monthly values are annual totals ÷ 12; daily values are annual totals ÷ 365. Actual demand varies. Comparisons cover the whole campus, including non-AI uses.

Water: see the numbers and sources

This is water used up, mainly through evaporation. Power-generation water may be used in a different watershed.

Total water use1,865M gal/yr
Evaporated on site168M gal
Making the power1,697M gal
Household comparison23,311homes, at 80,000 gal/year
Pressure on local water
Low — a regional measure of demand compared with available water
Where the water comes from
Surface water — river, lake or canal
Cooling
Closed-loop with river-water heat rejection
Basis
Modelled from cooling design — WUE 0.25 L/kWh
Claimed vs observed
0.129 million gallons a day authorised. Amazon asked for 0.55.
Air: see the numbers and sources

The totals include nitrogen oxides, sulphur dioxide and fine particles. They cover both this site and the power plants supplying it.

Nitrogen oxides15.8t/yr
Sulphur dioxide2.58t/yr
Fine particulates1.35t PM2.5
Health (EPA)$0.97M/yr
Health range
$0.34–0.97 million a year. Lower bound is EASIUR national mid-range; upper is EPA benefit-per-ton at a ~$12M VSL.
Statistical deaths
0.08 a year at that VSL — a national-average conversion from tons, not a local concentration study.
Equals
19,711 cars of NOx
Where it burns
Dedicated nuclear (co-located PPA)
Generation mix
Nuclear ~100%
Diesel backup
109 gensets, 88.6 MW standby. Test-hours term: 10.6 t NOx/yr (50 h at 30% load, 8 kg NOx/MWh).
Air permit
99.0 t/yr NOx enforced cap — 1.00 tons under the 100-ton Title V major-source line
CO₂e
30.8 kt/yr — climate, not air quality
The project, approvals and community concerns
Who asked for it
AWS — bought the campus from Talen Energy for $650M
Who approved it
FERC initially rejected the amended interconnection agreement in Nov 2024 over cost-shifting to other ratepayers; a restructured deal followed in 2025
Co-location
FERC rejected PJM's amended interconnection service agreement on 1 November 2024 that would have raised co-located load at Susquehanna from 300 MW to 480 MW.
What it serves
AWS compute co-located with a nuclear plant
IT capacity
300 MW current capacity / 960 MW full-build scenario

The test case for 'behind-the-meter' co-location: plugging a data center straight into a nuclear plant bypasses the grid, and FERC balked because everyone else still pays for the transmission system it stops using.

nuclear PPAratepayer-cost dispute

Keep this guide handy

41.0925°, -76.1447°

Quote or share these estimates

Gigawatt Ledger (2026). Cumulus / Susquehanna: water and air. https://gigawatt-ledger.pages.dev/site/susquehanna/. Modelled from disclosed capacity; site-level error ±40%.

Include the estimate’s date, whether it describes current or proposed capacity, and its uncertainty. Get an embeddable card.

Gigawatt Ledger · September 2026. Water and air figures are estimated from public records and disclosed capacity. How we calculate them · Use this in your community.